BASIC TROUBLESHOOTING GUIDE - FOR ADDITIONAL INFORMATION CONTACT
TECHNICAL SERVICES AT TELEPHONE NUMBERS LISTED BELOW
ALL LIGHTS FAIL TO ILLUMINATE - Check 120V power supply into transformer - Check for 12V
output at transformer - check or reset GFCI. Make sure 120 volts has not been used in the
installation of these lights - damage is assured and is NON WARRANTY.
ONE OR MORE LIGHTS DIM - This is generally caused by a poor connection or improper wire
gauge. To determine if light or lights has fault - separate each light from all other lights and
independently wire 12V to this light only. Repeat process on each light. If junction box is used -
recheck for proper connection of light cord. AGAIN IF A JUNCTION BOX IS BEING USED - VERIFY
THAT THE CORRECT WIRE GAUGE IS BEING USED BETWEEN TRANSFORMER AND JUNCTION BOX.
EVEN THOUGH OTHER LIGHTS MIGHT WORK CORRECTLY - IMPROPER WIRE GAUGE SIZE COULD
ALLOW 1 OR MORE LIGHTS TO WORK IMPROPERLY. Measure and verify that proper low voltage is
being supplied to lights - see WIRE GAUGE & WIRE LENGTH GUIDE CHART.
BLINKING, FLASHING, NON WORKING LIGHTS - This is generally caused by a poor connection
or improper wire gauge. To determine if light or lights has fault - separate light from all other lights
and independently wire 12V to this light only. Repeat process on each light. If junction
box is used - recheck for proper connection of light cord. AGAIN IF A JUNCTION BOX IS BEING
USED - VERIFY THAT THE CORRECT WIRE GAUGE IS BEING USED BETWEEN TRANSFORMER
AND JUNCTION BOX. EVEN THOUGH OTHER LIGHTS MIGHT WORK CORRECTLY - IMPROPER
WIRE GAUGE SIZE COULD ALLOW 1 OR MORE LIGHTS TO WORK IMPROPERLY. Measure and
verify that proper low voltage is being supplied to lights - see WIRE GAUGE & WIRE LENGTH
GUIDE CHART. MOST IMPORTANTLY SEE CHART FOR MIN/MAX VOLTAGE & CORD
LENGTH CHART.
2013/14 SAVI LED LIGHTING PRODUCTS
COLORED LIGHTS OUT OF SYNCH - Follow Synchronization Instructions in this Guide. Be very
patient and read instruction carefully. If lights fail to synchronize - verify that proper wire
connections are being achieved for those lights that are out of step with others. Generally a lights
failure to sync with the rest is: improper voltage supply or poor connection to light.
NOTE: In most situations problems come down to 4 main faults: improper voltage supply,
improper wiring gauge,improper/poor wiring connections or the light itself.
2013/14 SAVI LED LIGHTS ARE FIELD SERVICABLE AND THE CORD AND LIGHT BODY
FIXTURE SHOULD NOT BE REMOVED COMPETELY FROM THE CONDUIT OR POOL. THERE SHOULD
BE ENOUGH CORD SUPPLIED IN THE SERVICE LOOP TO REMOVE LIGHT FROM WALL FITTING AND
LIFTED ABOVE WATER LEVEL FOR LED LIGHT CARTRIDGE REPLACEMENT. IF THERE IS NOT
ENOUGH CORD IN SERVICE LOOP OR IT CANNOT BE ACCESSED - POOL WATER CAN BE DRAINED
BELOW LIGHT TO ACCESS FRONT OF LIGHT.
DO NOT PULL LIGHT AND CORD ENTIRELY FROM CONDUIT UNLESS INSTRUCTED BY COMPANY.
SAVI POOL AND SPA WILL NOT ACCEPT ENTIRE LIGHTS BEING RETURNED FOR SERVICE
UNLESS INSTRUCTED BY COMPANIES TECHNICAL SERVICES DEPARTMENT
ONLY LED LIGHT CARTRIDGES SHOULD BE REPLACED OR EXCHANGED WITH THE
2013/14 PRODUCT
Refer to the Light Cartridge Replacement Instructions included in this Guide for light replacement.
WARNING: All servicing of SAVI LED Lights should be done by a licensed or certified electrican or
a qualified pool professional in accordance with the National Electric Code (NEC) or Canadian
Electric Code (CEC)
For additional troubleshooting assistance or installation advice please contact Technical
Services at telephone number below.